microSpider IndustrialThe microSpider Industrial has been superseded by the microSpider2 Industrial

The microSpider Industrial is a complete data logging and telemetry system. It includes all software, hardware, backup battery and a built-in mobile phone module. The enclosure fits standard DIN rail brackets.

The microSpider Industrial can

  • monitor inputs (analogue, digital, counters, frequency, quadrature/shaft encoder)
  • control outputs
  • generate SMS, email and twitter alarms
  • record data
  • send data via e-mail or FTP
  • communicate via internal GSM/NextG/LAN module
  • be used in wet environments
  • operate for more than 5 years on its replaceable internal battery
  • update software automatically in-field from remote servers, or update from connected pc.

The microspider industrial is ideal for long term monitoring and can interface with a wide range of sensors and meters. the browser interface makes it easy to set up and test. it can be powered from 12v dc.

the microspider industrial logs data and automatically sends reports via email or ftp.  any alarms can activate outputs, send sms and email alarm messages as well as historical reports

 

benefits

economical – low upfront, installation and operational costs

Easy to use – simple familiar web browser interface

Easy to install

Integrated mounting – DIN rail compatible.

Simply connect antenna, battery / supply and inputs.

No special software required

setup and download using browser

reports sent straight to your PC or server

text/csv reports open in Excel

receive reports via email or FTP

No licenses, royalties or service agreements

Large internal memory – full local backup of data

General

Physical

Dimensions: (approx) 156(L) x 60(H) x 87 (W) mm

Weight: (approx) 500 g

Operating temperature: -5 to +50 degrees Celsius

Data Recorder

Capacity: approximately 400,000 records

Storage memory: Non-volatile FLASH

Time resolution: 1 second

Download format: CSV file

Battery

Internal 9V Recovery Battery (optional)

External Battery / Power Supply

Battery Charger (Optional)

Warranty

Factory backup 12 months parts and labour guarantee

Inputs/Outputs

Inputs

Number of inputs:

  • 4 multi-type
  • 4 system inputs

Multi-type: Digital, analogue, counter, event, quadrature/shaft-encoder (individually user definable)

Digital Inputs: Type 0 -12V DC Voltage or voltage-free switch contact

Analogue Inputs: Resolution 12 bits

  • 4 - 20 mA, common ground
  • 0 - 1V, common ground
  • 0 - 2.5V, common ground
  • 0 - 5V, common ground
  • 0 - 10V, common ground

Counter / Event Inputs

  • Minimum pulse width: 10 ms
  • Range: 0 - 999,999

System Inputs:

  • System temperature
  • Battery voltage

Outputs

Number of outputs 3 

  • 1 x open collector
  • 1 x high side power switch
  • 1 x low voltage power supply (3.3V/5V selectable)

Alarms/Comms

Alarms

Number of alarms: 8

Type: SMS, twitter and/or e-mail transmission

Trigger: User definable input and trigger point

SMS / e-mail / twitter text: 1 per alarm, user definable

Number of phone numbers: 3 per alarm, user definable

Number of e-mail addresses 2 per alarm, user definable

Communication Interfaces

Ethernet 10 base-T, RJ-45 connector on comms cable

Cellular phone module: Built-in GSM or NextG

Antenna: internal antenna - standard, external antenna - option

Internet connectivity: GPRS or 3G (modem type and network dependent)

Options

Product is available in a variety of configurations to suit your needs, you may specify any of the following:

  • NextG or GSM modem
  • With or without battery charging circuitry.

Downloads

Software

Software for microSpider Industrial may be downloaded using the inbuilt Automatic Upgrade System. If a software file is required for manual upgrade purposes, please contact Halytech to discuss.

Manuals / Brochures

microSpider Industrial Brochure

microSpider Manual V2.01

 

 

News

March 2017

In response to customer requests, Halytech has implemented the Distributed Network Protocol (DNP3) for its microSpider2 and hydrospider2 data loggers, making it easy to fully integrate the loggers into centralised SCADA systems.

Read more ...

Contact Us

Unit 11, 22 Lexington Drive
Norwest Business Park
Bella Vista NSW 2153

9:00 - 5:00 Monday to Friday

phone +61 2 8814 5235

This email address is being protected from spambots. You need JavaScript enabled to view it.

This email address is being protected from spambots. You need JavaScript enabled to view it.